Analog inputs

• Three phase currents: 5/1 A programmable

• Ground current: 5/1 A programmable or 0.2 A

Rated frequency: 60/50 Hz programmable

• Three-phase and ground voltages: programmable

nominal secondary voltage (available as options)

Binary inputs and outputs

• Four, eight with VT inputs, binary inputs standard

• Two NO outputs with trip circuit monitoring

• Three NO outputs

• One Form C output and self-check alarm output

• Additional binary inputs and outputs available as options

Tools

• PCM600 V2.8 for setting, configuration and data retrieval

• COM600 Station Automation series products V5.0

• Web browser based user interface (IE 11 or later)

Certificates

• UL Listed product, File E103204

Control voltage

• Option 1: 48 … 250 V dc, 100 … 240 V ac

• Option 2: 24 … 60 V dc