Technical Data SA 801F

Input voltage Alternating current 115 – 230 VAC

Permissible range 90 – 260 V AC

Frequency: 50 – 60 Hz (47 – 63 Hz)

Input current at

nominal load 230 V AC: 210 mA

115 V AC: 411 mA

Rated input power 48 VA

Backup energy for

the event of

power failure > 20 ms

Fuse Subminiature fuse 2.5 AT, soldered

Output voltage 3.3 V DC (± 3%) typical

5 V DC (± 3%) typical

Output current 0.5 – 5 A to 3.3V and 5.0 V

Current limit approx. 6 A

Automatic return to normal operation after

short circuit

Total output power max. 26.5 W

Weight 0.460 kg

Technical Data SA 811F

Input voltage Alternating current 115 – 230 VAC

Permissible range 90 – 260 V AC

Frequency: 50 – 60 Hz (47 – 63 Hz)

Input current at

nominal load 230 V AC: 275 mA

115 V AC: 541 mA

Rated input power 63 VA

Backup energy for

the event of power failure > 20 ms