PLC control of AF400 and above
Make sure the dip switch is in the correct position for proper operation See picture
below. Position A when using PLC control and position B for conventional operation (default).
High temperature readings
When concern of high temperatures on and around the contactor please check
the following (also see picture below for max permitted temperatures).
• Make sure the connections are properly torqued.
• Make sure the cable size is what is recommended in our catalogs.
• Make sure the correct coil is selected for the applications.
Measurement of the resistance of the main contacts is not recommended since only
advanced equipment can be used to get a correct reading. Due to the location of the
armature the cover can reach very high temperatures (>100C). This is still within
acceptable limits.