The system can be fitted with control buttons and mode changeover switches mounted separately on the instrumentation door of the switchboard cabinet.
Manual/automatic/parallel switching is achieved by means of a mode switching button.
The system can be switched automatically according to a predefined procedure or switched to manual mode to exit automatic operation.
In the event of planned maintenance or power failure, manual parallel switching of the power supply is also possible to ensure that important loads are not interrupted by the switching process, thus ensuring continuity of the power supply.
Measurement functions
The Emax 2 Ekip Touch is equipped with a measurement module, which automatically collects and measures the status and parameters of the power supply and displays them visually on the circuit breaker’s LCD screen.
Status indication
The Emax 2 Harness system can also be equipped with a status display function to show the operating status of the system to the user, which is convenient for on-site management.
Voltage Status Indication: The line voltage status of power supply 1/power supply 2 can be indicated by the LEDs. If the power supply voltage status is normal, the indicator light will be always on; if the voltage is abnormal (under/over-voltage), the indicator light will not be on.
Circuit breaker status indication: The status of power supply 1/power supply 2 (normal/abnormal) and the status of CB1/CB2/CB3 actuating circuit breakers (bright – closing; non-bright – opening) are visually displayed in the form of a single-line diagram of the system.