Data recorder (optional)

The data recorder can log analog inputs, digital inputs, and digital out

puts. The recorder has the following settings:

•  number of samples (6-72)

•  recording period (5-60 sec)

•  pre-trigger (0-100%)

•  trigger event (start for recorder)

•  trigger event (stop for recorder)

The recording period depends on the number of samples. The recorder

can be set with the pre-trigger to record event data even before the

event happens.

Diagnostics and monitoring

SYMAP® provides various diagnostic and monitoring functions:

•  all memories (ROMs, RAMs, EEPROMs)

•  all analog reference voltages

•  automated test sequences

•  control power ON/OFF

•  binary input and output for control logic

The following supervising systems are offered by SYMAP®:

•  self-diagnostics

•  inputs of analog data (auxiliary circuit)

•  status and position of switching device and motor’s on-off status

•  supervising supply of trip coil

•  gas pressure

• temperature inside panel

•  each operating life of breaker (hours)