Introduction
The AZ100 Zirconia Oxygen Analyzer is a versatile system designed primarily for the OEM boiler and burner controls market.
The system is a low-temperature type designed to work in process temperatures up to 800 °C (1472 °F) and with a maximum sensor mounting flange temperature of 400 °C(752 °F).
The analyzer provides oxygen computation, with readout and retransmission, based on the probe mV output signal. The output signal (E mV) is Nernstian in form and follows the equation:
E (mv) = 0.0496T(log10 P0 / P1) ± CmV
Where: T = Absolute temperature
P0 = Reference O2 partial pressure
P1 = Sample O2 partial pressure
C = Cell constant (mV zero offset)
0.0496 = Faraday’s gas constant
Probe design
The probe uses the proven and innovative ABB electrode and cell design technology which has been so reliable in other ABB zirconia probe designs.
The flexible probe design gives a range of intake tube lengths to suit all applications and an optional filter/flame arrester making it safe for use where groups IIB and IIC gases may occur in the process being measured.
The probe has options of male thread NPT or BSPT mountings. As with all previous ABB designs of low temperature probes, the AZ100 probe is site-serviceable.