Comment:
A slave fitted solely with binary channels occupies 1 connection point.
A slave fitted with binary and analog channels occupies 2 connection points of the available 31.
The maximum number of remote ANALOG units depends on the MASTER central unit:
– 50 series: – a maximum of 31 remote analog input units
– a maximum of 31 remote analog output units
– a maximum of 15 extensible remote units (ICMK14F1) with analog input / output
extensions + 1 remote analog input / output unit (15 x 2 + 1 = 31)
– or a mixed binary / analog configuration within the previous limits
– 90 series: – a maximum of 12 remote analog input units
– a maximum of 12 remote analog output units
– or a maximum of 12 slaves with analog extensions
Operation of the 40 and 50 series central units