Voting Units
The Voting Units SS822Z, SS823 and SS833 have been
specifically designed to be employed as a control
unit within a redundant power supply configuration. The output connections from two Power Supply
Units are connected to the Voting Unit. The Voting
Unit separates the redundant Power Supply Units, supervises the voltage supplied, and generates supervision signals to be connected to the power consumer.
Green LED’s, mounted on the front panel of the voting unit, provide a visual indication that the correct
output voltage is being delivered. Simultaneously
with the green LED illuminating, a voltage free contact closes the path to the corresponding “OK connector”. Voting Unit trip levels, are factory preset.
High Integrity
The AC 800M High Integrity and the connected S880
High Integrity I/O system (including field power)
shall be supplied from a SELV or PELV power supply
(e.g. SD83x) connected through the power voter
SS823. The SS823 Voting Unit has double overvoltage protection circuit, limiting the output voltage to
max 30 VDC. It is also able to detect both short and
open circuit in the voting element.
The SS822Z and SS823 units is also G3 compliant.