• Synchrocheck and dead-line check function for single- or multi-breaker arrangements:

– Selectable energizing direction

– Two functions with built-in voltage selection

– For automatic or manual synchrocheck and with different settings

• Auto-reclosing function for single- two-, and/or three-phase reclosing:

– Two functions with priority circuits for multi-breaker arrangements

– Co-operation with synchrocheck function

– Can be switched On-Off from remote through communication or with local switches through binary inputs

• Selectable additional software functions such as distance protection, control and monitoring

• Built-in data communication modules for station bus IEC 61850-8-1

• Data communication modules for station bus IEC 60870-5-103. LON and SPA

• Integrated disturbance and event recorder for up to 40 analog and 96 binary signals

• Time synchronization over IEC 61850-8-1. LON,SPA, binary input or with optional GPS module

• Analog measurements accuracy up to below 0.5% for power and 0.25% for current and voltage and with site calibration to optimize total accuracy

• Versatile local human-machine interface

• Extensive self-supervision with internal event recorder

• Six independent groups of complete setting parameters with password protection

• Powerful software PC tool for setting, disturbance evaluation and configuration

• Remote end data communication modules for C37.94 and G.703