Features
• A protection, control, and monitoring IED with extensive functional library and configuration
possibilities and expandable hardware design to meet specific user requirements
• For power transformers, autotransformers, shunt reactors, T-protection, generator transformer
blocks, phase shifting transformers and small busbar systems
• For two- and three-winding transformers with up to six stabilized inputs
• For multi- or single-breaker arrangements
• Transformer differential protection with:
– Percentage bias restraint for through faults
– Waveform and Second harmonic restraint for transformer inrush
– Fifth harmonic restraint for overexcitation
– High sensitivity for interturn faults
• Restricted earth fault protection for all direct or low impedance earthed windings
– Extremely fast operation
– High sensitivity
– High and low impedance based
• Full scheme phase-to-phase and phase-to-earth distance protection with up to five zones:
– Load encroachment feature
• Instantaneous high speed short circuit function with low transient overreach