Optional function
Communication on MODBUS RTU Protocol
Other Functions
Self Supervision
The IED is provided with an extensive self-supervision system which
continuously supervises the software and the electronics.
It handles runtime fault situations and informs the user about an existing fault via the LHMI.
When in an IED internal fault is detected, the green Ready LED ceases to
glow and the self-supervision output contact is activated. Internal fault
indications have the highest priority on the LHMI. None of the other
LHMI indications can override the internal fault indication. An indication
about the fault is also shown as a message on the LHMI. The text IRF with
an additional text message, a code is shown to indicate the fault type.
The user can try to eliminate the fault by restarting the IED. If the fault is
still found, the IED stays in internal fault mode. All other output contacts
are released and locked for the internal fault.
The self-supervision signal output operates on the closed circuit principle.
Under normal conditions the relay is energized and the contact gap 5-6 in
connector XK2 is closed. If the auxiliary power supply fail or an internal
fault is detected, the contact gap 5-6 is opened.