Low Voltage Directive

This product is tested to meet Council Directive 73/23/EEC

Low Voltage, by applying the safety requirements of EN 61131–2

Programmable Controllers, Part 2 – Equipment Requirements and Tests.

For specific information required by EN 61131-2, see the appropriate

sections in this publication, as well as the following Allen-Bradley publications:

Industrial Automation Wiring and Grounding Guidelines 

(for noise immunity), publication 1770-4.1

Automation Systems Catalog, publication B111

Wiring the Module

Installing the Ferrite Collar

For immunity to electrical noise with this CE-marked module, insert

ferrite collar (Fair-Rite Inc. part number 0443164151) around the input

cables immediately beneath the module in the I/O chassis. 

Do this as follows:

1. Bundle the cables at the module end.

2. Fold the collar so that it encircles the cables.

3. Press the plastic housing until the collar snaps together.

4. Check that the collar is fully latched.

5. If the collar slides on the cables, use a cable tie to secure it.