SPECIFICATIONS

Power supply …………………………………………………..12/24 VDC (8 to 40 VDC)

Intrinsic consumption ………………………………….  max. 14 W (LT: max.22W)

Ambient temperature (operation) ……………. -20 to 70 °C (LT: -40 to 70 °C)

Ambient temperature (storage) …………………… -30 to 80 °C / -22 to 176 °F

Ambient humidity………………………………………………. 95%, non-condensing

Voltage (software configurable) …………………………………………….. ( /)

100 Vac  Rated (Vrated) …………………………………….. 69/120 VAC

Max. value (Vmax) …………………………………….. 86/150 VAC

and 400 Vac  Rated (Vrated) …………………………………… 277/480 VAC

Max. value (Vmax) …………………………………… 346/600 VAC

Rated surge volt. (Vsurge) ……………………………………………. 4.0 kV

Accuracy …………………………………………………………………………… Class 0.5

Measurable alternator windings … 3p-3w, 3p-4w, 3p-4w OD, 1p-2w, 1p-3w

Setting range ………………… primary …………………………… 50 to 650.000 VAC

Linear measuring range …………………………………………………….. 1.25×Vrated

Measuring frequency……………………………………….. 50/60 Hz (40 to 85 Hz)

High Impedance Input; Resistance per path …………………………….. 2.0 M

Max. power consumption per path ………………………………………… < 0.15 W

Current (Isolated, software configurable)     Rated (Irated) ……… 1A or 5A

Linear measuring range ……………………………………………….. Igen = 3.0×Irated

Imains/ground = 1.5×Irated

Setting range ……………………………………………………………….. 1 to 32.000 A

Burden ……………………………………………………………………………… < 0.10 VA

Rated short-time overcurrent (1 s) ……………………..[1] 50×Irated, [5] 10×Irated

Accuracy ………………………………………………………………………….. Class 0.5

Power ……………………………………………………………………………………………

Setting range …………………………………………………. 0.5 to 99.999.9 kW/kvar

Accuracy …………………………………………………………………………… Class 1.0

Discrete inputs …………………………………………………………………… isolated

Input range ……………………………………………………..12/24 VDC (8 to 40 VDC)

Input resistance …………………………………………………….. approx. 20 kOhms

Relay outputs ………………………………………………………………………… isolated

Contact material ……………………………………………………………………….. AgCdO

Load (GP) ………………………………………………………………. 2.00 AAC@250 VAC

2.00 ADC@24 VDC / 0.36 ADC@125 VDC / 0.18 ADC@250 VDC