Module Operation
The thermocouple module input circuitry consists of four differential
analog inputs multiplexed into a single analog-to-digital (A/D)
convertor. The mux circuitry also continuously samples the CJC A and
CJC B sensors and compensates for temperature changes at the cold
junction (terminal block). The figure on the following page shows a
block diagram for the analog input circuitry.
The A/D convertor reads the selected input signal and converts it to a
digital value. The multiplexer sequentially switches each input
channel to the module’s A/D convertor. Multiplexing provides an
economical means for a single A/D convertor to convert multiple
analog signals. However, it does affect the speed at which an input
signal can change and still be detected by the convertor.