During operation, the velocity sensor signal
(23 mV/mm/s) is converted by a preamplifier into
a standardized voltage signal (70.7 mV/mm/s). It
then passes through high-pass and low-pass filters
before being amplified by a two-step wide-band
amplifier to the level essential to the electronic
circuitry. It is user-configurable DIP switches that
determine which of the two possible
measurements/units – velocity or displacement –
is used for the vibration monitoring.
The DC-output signal (current loop output) is
available after true RMS rectification (RMS units).
The DC-output signal also acts with two
adjustable alarm level limit level detectors. The
response delay of the alarms/relays is set by DIL
switches to 1, 3, 5 or 10 seconds. The relays’
change-over contacts enable the Alert and
Danger circuits to operate as ether normally
energized (NE) or normally de-energized (NDE),
again, as set by DIL switches.
Accordingly, the VMS 830-2 vibration monitor is
recommended for the monitoring and protection
of stand-alone machines and auxiliary balance of
plant (BOP) equipment such as fans, pumps,
centrifuges, mills and gears. Among other things it
allows observation according to ISO 10816
(DIN 45665).