IEC-101 to IEC-104 conversion
With ARC600. conventional IEC 60870-101 serial devices can
be attached to a modern TCP/IP based IEC 60870-5-104
control system. This is enabled by the protocol conversion
from IEC 60870-5-101 to IEC 60870-104. In this case,
ARC600 (IEC-101 master) uses local synchronous data
polling where it continuously sends requests and the IEC-101
device (IEC-101 slave) responds. In the direction of the
control room, the communication protocol is IEC-104 and
ARC600 can send events asynchronously as they arise while
SCADA performs only slow-period background scans.
Another advantage of the local protocol conversion is an
advanced data acknowledgement mechanism. IEC-104
allows multiple packets, and multiple events in a single
packet, to be acknowledged collectively and the packets can
be buffered up to the time of acknowledgement from SCADA.