Accuracy:
Voltage mode: 0.125% of full scale from 0° to 60°C
Current mode: 0.225% of full scale from 0° to 60°C
Digital Filtering Time Constant: 0.3 Sec
DC Input Resistance:
Voltage mode: 780kW
Current mode: 250W
Repeatability: 0.003125%
Common Mode Rejection:
>120db @ 60Hz (digital filtering disabled)
Normal Mode Rejection:
>40db @ 500Hz (digital filtering enabled)
Isolation:
1500VDC channel-to-PLC
140Vrms channel-to-PLC
Output Specifications:
Output Channels: 4 analog output channels
Output Range:
Unipolar: 0 to 5VDC, 0 to 10VDC, 0 to 20mA
Bipolar: -5 to +5VDC, -10 to +10VDC, or -20 to +20mA
Resolution:
Unipolar 12 bits:
0 – 5VDC range = 1.25mV/step
0 – 10VDC range = 2.5mV/step
0 – 20mA range = 5µA/step
Bipolar 12 bits:
-5 to +5VDC range = 2.5mV/step
0- 10VDC range = 5.0mV/step
-20 to +20mA range = 10µA/step
Accuracy:
Voltage mode: 0.125% of full scale from 0° to 60°C over total load range
Current mode: 0.225% of full scale from 0° to 60°C over total load range
Capacitance Drive: 0.01 microfarad
Load Resistance:
Voltage mode: 1kΩ minimum, no maximum
Current mode: 0kΩ to 1kΩ max. @ 24VDC
or greater
User Supply: 20 to 30VDC @ 0.25 Amps
(maximum ripple of 0.4V)
UL Class 2 power supply
Isolation:
1500VDC channel-to-channel
1500VDC channel-to-PLC
Leave a comment