Closing time delay
The minimum closing time, set at 100 ms, is actually 160 ms, as it is necessary to add the time required by
the measurement units and the operation of the output relays to the set 100 ms. It should be kept in
mind that during the first cycles, from the time of a closure, the voltage is stabilizing both in the line as
well as in the buses and it is no desirable to allow a closure under these conditions. What is more, it is
necessary to take into consideration the response of both the high voltage transformers and the internal
transformers of the relay.
There is also a time for sustaining the permission signal, which always has a fixed value of some 130 ms.,
being the result of a prefixed delay of 100 ms. added to the dropout time of the measurement units (one
cycle = 20 ms. at 50 Hz.) and the deactivation of the output relay (10 ms.).
Minimum settings
Barring any special requirements, it is not recommended to use settings that near the minimum limits for
the relays, (2 V for the voltage difference, 2º for the angle difference), so as to avoid being too restrictive
in close enabling, given the real characteristics of accuracy in the installations, measurement transformers,
etc.