Required Tools and Equipment
Have the following tools and equipment ready:
• medium blade screwdriver
• termination kit (the package, containing resistors and a ring lug, which was
included with the scanner)
• approximately 38 cm (15 inches) of #20 AWG wire for grounding the drain
shield to the SLC chassis (for Series A retrofits)
• adequate length of RIO communication cable (Belden™ 9463) for your
specific application
RIO Link Wiring
The scanner is connected to other devices on the RIO link in a daisy-chain (serial)
configuration. There are no restrictions governing the space between each device,
provided the maximum cable distance (Belden 9463) is not exceeded. A 1/2 watt
terminating resistor (included with the module) must be attached across line 1 and
line 2 of the connectors at each end (scanner and last physical device) of the RIO
link. The size of the resistor depends on the baud rate and extended node
capability, as shown in the table below.
Note: To use extended node, all devices on the RIO link must support it. Refer to
each device’s user manual.