Listed by category, the following is a complete list of the
function blocks available with the EIOC.
Advanced Control – None
Advanced Functions – State Transition, Step Sequencer
Analog Control – Analog Tracking, Calc/Logic, Filter,
Input Selector, Scaler, Signal Characterizer, Signal Generator,
Signal Selector, Bias/Gain, Manual Loader, PID, Rate Limit,
Ramp, Enhanced Ramp, Splitter, Limit
Energy Metering – None
IO – Alarm Detection, AI, AO, DI, DO
Tag I/O – DI, DO, AI, AO
Logical – All
Math – All
Special Items – All
Timer Counter – All
Access to DeltaV Live graphics, DeltaV Operate graphics, and
the alarms and history collection from EIOC control modules
follows the same rules and mechanisms as control modules
running in the controllers in a DeltaV System.
The EIOC mounts on the dual horizontal carrier, which includes
redundant Power input Terminals as well as redundant
Ethernet Isolation ports. The Ethernet Isolation ports isolate
the redundant DeltaV Control Network communication
from the redundant Ethernet Device Networks. An Industrial
Networks Firewall is recommended to provide added security
based on deep packet inspection to restrict communications
at the Ethernet device and Ethernet protocol level. In this way,
Robustness and Security is ensured.