When configuring the EIOC Control Modules, all typical
Function blocks needed for continuous operation are available;
however, the usage of the following Function blocks are limited
in the EIOC:
256 DC’s, EDC’s and DCC’s – used for such applications as
motor control in MCCs.
26 PID’s – analog control where all or most of the signals are
coming from Ethernet Devices.
16 SEQs – Sequence function block used for sequencing
motor control states.
16 STDs – State Transition Diagram used in sequencing and
can be used with the SEQ function blocks.
Batch control, SFCs, PLMs, and Equipment Modules are not
supported in the EIOC.
To maintain the capacity of the EIOC, consideration should be
taken to keep modules as lean as possible. Heavy configuration
in the modules will decrease the capacity of 2000 modules in
the EIOC.