Protection functions
The protection relay offers integrated protection functions including two-stage
overvoltage and undervoltage protection, two-stage residual overvoltage protection,
as well as singlestage negative phase-sequence overvoltage protection and
single-stage positive phase-sequence undervoltage protection.
Measurement
The protection relay physically measures the three phase-tophase voltages and the residual voltage of the power system.
Further, from the phase-to-phase voltages the protection relay
calculates the positive and negative phase-sequence voltages,
the one-minute average phase-to-phase voltage, the average
phase-to-phase voltage for a user-specifiable time frame, the
maximum value of the one-minute average voltage, and the
maximum and minimum phase-to-phase voltage value since last reset.
The values of the voltages measured or calculated can be
accessed locally via the user interface on the protection relay’s
front panel, or remotely via the serial communication interface
on the rear panel of the protection relay.
Disturbance recorder
The protection relay is provided with a built-in battery backedup digital
disturbance recorder for four analog signal channels and eight digital signal channels.
The analog channels can be set to record the curve form of the voltages measured.
The digital channels can be set to record external or internal relay
signals, for example the start or trip signals of protection relay’s
stages, external blocking or control signals. Any digital relay
signal such as a protection start or trip signal, or an external
relay control signal can be set to trigger the recording.
The recordings are stored in a nonvolatile memory from which the
data can be uploaded for subsequent fault analysis.