Connection Solutions
Several accessories are available with 460 volt 1326 cables. This
section highlights the most common application used with each
accessory, including:
• Right-angle connection.
• CE-compliant in-line connection.
• Remote in-line connection.
• Harsh environment connection.
• Double-ended bulkhead in-line connection.
Right-Angle Connection
This solution provides a low-profile right-angle connection at the motor
Linear-flex is defined as flex in one direction. The flex-rated cable is
not rated for twist-flex, which is flex in two directions. Power track
(linear-flex) cabling must not be used in twist applications.
Standard Allen-Bradley cables—1326-CCU-xxx for commutation and
1326-CPB1-xxx or 1326-CPC1-xxx for power—are tray-rated
(stationary) and should only be used for one-time flex applications.
• Power track cabling is required for applications where dynamic
linear flexing occurs. Use the following cables for these applications:
• 1326-CCUT-xxx (commutation for all motors)
• 1326-CPB1T-xxx (power for 1326AS-B3xxx and 1326AS-B4xxx motors)
• 1326-CPC1T-xxx (power for 1326AS-B6xxx and 1326AS-B8xxx motors)