Resolution

• 16 bits

Common mode rejection

• >87 dB @ 50/60 Hz

Series mode rejection

• >50 dB @ 50/60 Hz

Common mode voltage between channels

• ± 5 V (max.)

Absolute maximum input voltage

• ± 30 V

Isolation (any channel to Railbus)

• 60 V peak

CONFIGURABLE PARAMETERS

Sensor type

• User selectable

Alarms

• High and low

Input dead zone

• User defined value

Selectable input filtering

• Off / 2 reading avgerage / running avgerage

Drive on open circuit fault

• Disabled / upscale / downscale

Channel status

• Active / Inactive

Cold junction compensation

• Enable / disable / channel number

RESPONSE TIME

Analog signal change to availability on Railbus

• 600 ms (max.)