Welcome to the official website of CNIACS Automation Technology Co., Ltd!

Fanuc IC660BBA100 Analogue Input/Output Module

The IC660BBA100 analogue input/output block also provides an optional input filter time of up to 1024 milliseconds.

Each output can be left in its final state or at its default value if the communication process is interrupted.

It is backward compatible with its earlier versions, as well as with the GE family of IC697. IC600. and IC550 PLCs.

Replacing the module’s electronics eliminates the need to change the module’s field wiring and configuration.

The IC660BBA100 analogue input/output module has a 12-bit analogue-to-digital converter that converts the input signal current or voltage to a digital value.

The converted signal can be scaled to an integer for representation in engineering units.

The output circuitry is connected to a 12-bit digital-to-analogue converter, which converts the processed value to a voltage or current output signal.

The IC660BBA100 analogue I/O block also automatically calibrates the 2 converters to ensure accurate performance.

It transmits 8 bytes of input data and 4 bytes of output data during each bus scan.

The user can monitor the input and output values in integer form via a handheld monitor.

Connect AC power to terminals 6 and 7 to supply power to the module.

Be sure to connect a 250 volt, 1/8 amp fuse in series with the power connector.

The 2 LED status indicators on the panel show the status of the module.

Fanuc IC200MDD845 Hybrid I/O Module

Description: The IC200MDD845 is a 24-point modular discrete I/O module in the VersaMax I/O family.

Formerly manufactured by GE Intelligent Platforms, now part of Emerson Automation.

The module has sixteen (16) 24 VDC positive logic inputs and eight (8) independently isolated Type A 2.0 Amp relay contact outputs.

The module has a maximum backplane current draw of 270 mA.

The IC200MDD845 is a combo I/O module in Emerson Automation’s VersaMax product line.

The module can be used as part of a VersaMax distributed I/O station or as part of a VersaMax control system using a local CPU module.

As a combo I/O module, the IC200MDD845 has a total of 24 input and output channels, of which 16 input channels support positive logic.

16 of the input channels support positive logic wiring and can accept 24 VDC nominal signal voltage; and

8 A-type or normally open (N.O.) contact outputs, rated at 2.0 amps, support 5/24/125 VDC and 120/240 VAC nominal voltage turn-on.

The allowable voltage range is 0-125 VDC and 0-265 VAC.

The IC200MDD845 has a maximum backplane current consumption of 270 mA, with individual LED status indicators for each input and output channel.

Each input and output channel has a separate LED status indicator that allows local monitoring of the startup and power-up status of each channel of the module.

There is also an OK LED on the module to indicate that backplane power is being continuously supplied to the IC200MDD845.

ABB New VD4 Medium Voltage Vacuum Circuit Breaker


Operating mechanism type EL

The low speed of the contacts, the short running time and the low mass limit the energy required for operation and thus ensure extremely limited wear of the system. Circuit breakers

therefore require only limited maintenance.

VD4 circuit breakers have a mechanical operating mechanism with energy storage and free tripping. These features make opening and closing operations independent of the operator.

The operating mechanism is very simple to conceive and use, can be customised with various accessories and is quick and easy to install. This simplicity makes the equipment more reliable.

Structure

The operating mechanism and the magnetic poles are fixed to a metal frame which also serves as a support for the fixed circuit breakers.

The compact construction ensures robustness and mechanical reliability.

The tractable circuit breakers are also equipped with a bracket trolley for putting them into or taking them out of the switchgear or enclosure with the door closed.

– Vacuum interrupter technology

– Vacuum contacts protect against oxidation and contamination

– Vacuum interrupters embedded in resin poles

– The interrupters are protected against vibration, dust and humidity.

– Poles sealed for life

– Operation in different climatic conditions

– Limited switching energy

– Energy storage operating mechanism with anti-pumping device as standard

– Simple customisation with a full range of accessories

– Fixed and withdrawable

– Compact dimensions

– Compact dimensions Robust and reliable

– Limited maintenance

– Doors closed when circuit breakers are racked in and out

– Special locks on the operating mechanism and forklift truck prevent incorrect and dangerous operation

– High environmental compatibility

ABB VD4 Medium Voltage Vacuum Circuit Breakers Quenching Principle for Arc Extinguishing Chambers

ABB Arc Extinguishing Principle for Arc Extinguishing Chambers

In a vacuum arc extinguishing chamber, the arc starts at the moment of contact separation and is maintained until zero current is applied and may be affected by magnetic fields.

Vacuum Arc – Diffuse or contracted after contact separation, a single melting point is formed over the entire surface of the cathode, generating the metal vapour that supports the arc.

A diffuse vacuum arc is characterised by expansion of the contact surfaces and uniform distribution of thermal stresses across the contact surfaces.

At the rated current of the vacuum interrupter, the arc is always diffuse. Contact erosion is very limited and the number of current interruptions is very high.

As the value of the interrupting current increases (above the rated value), the arc changes from a diffuse to a contracting type due to the Hall effect.

Starting at the anode, the arc contracts and gradually becomes defined with further increases in current.

In the vicinity of the area in question, the temperature rises, which causes thermal stress on the contacts.

To prevent overheating and erosion of the contacts, the arc needs to remain rotating. As the arc rotates, it becomes similar to a moving conductor through which current passes.

Spiral geometry of ABB vacuum interrupter contacts

The special geometry of the helical contact generates a radial magnetic field in all areas of the arc column and concentrates it around the circumference of the contact.

Spontaneously generated electromagnetic forces acting in a tangential direction cause the arc to rotate rapidly around the contact axis.

This means that the arc is forced to rotate and involves a wider surface than a fixed contracting arc.

All this makes contact erosion negligible, except for minimising thermal stresses on the contacts.

Most importantly, the arc extinguishing process can be controlled even in the case of extremely high short circuits.

ABB vacuum interrupters are zero-current interrupters, which do not produce any re-strikes.

At zero current, the current charge is rapidly reduced and the metal vapour condenses, thus restoring the maximum dielectric strength between the interrupter contacts in microseconds.

VD4 circuit breakers have passed the following tests to ensure the safety and reliability of the equipment when used in any installation environment.

– Type tests: heating, industrial frequency withstand voltage insulation, lightning impulse withstand voltage insulation, short-time and peak withstand voltage current,

Mechanical life, short-circuit current generation and breaking capacity, no-load cable disconnection.

– Individual tests: main circuit insulation at working frequency voltage, insulation of auxiliary circuits and operating mechanisms, main circuit resistance measurement, mechanical and electrical operation.

ABB SPAM150C Motor Protection Relay

Brief Introduction

The SPAM150C Motor Protection Relay is a general purpose combination relay designed primarily for the protection of AC motors for a variety of applications.

It combines a large number of protection functions in one unit. The relay provides a complete set of protection against motor damage caused by various electrical faults.

The relay is also suitable for other equipment requiring thermal overload protection, such as cable or power transformer feeders.

Summary of Protection Functions

The relay thermal overload unit protects the motor against short- and long-term overloads. The maximum permissible continuous load depends on the setting value 1.

Normally this setting value is taken as the rated full load current (FLC) of the motor at an ambient temperature of 40°C. The motor can be overloaded for a short period of time if the motor is not loaded.

When the motor current increases to 1.05I under the above conditions, the thermal overload unit starts after a certain delay.

If the ambient temperature of the motor is below 40°C for a long period of time, the setting value I. can be set to .05…1.10 times the full load current (FLC) of the motor. 1.10 times.

The short-time overload phenomenon mainly occurs during the starting process of the motor. The motor is normally allowed to start twice under cold conditions and once under hot conditions.

One start is permitted under hot conditions, therefore, depending on the starting time of the motor, an integrating value t determining the characteristics of the thermal overload unit can be derived.

This value can be easily determined from the time/current graph in the hot state. t curve is selected from the starting current versus the corresponding starting time (with an appropriate margin).

The t-curve is selected from the starting current versus the corresponding starting time (with an appropriate margin). Using the same value of t, the total permissible starting time of the motor under cold conditions can be found from the cold curve.

ABB SPAJ140C Combined overcurrent and earth fault relay

Function

– Three-phase, low-setting phase overcurrent device with timed or inverse definite minimum time (IDMT ) characteristics

– Three-phase, high setting phase overcurrent device with instantaneous or timed characteristics

Operation

– Low-level ground fault device with timed or inverse deterministic minimum time (IDMT) characteristics

– High-level ground-fault unit with instantaneous or definite-time operation

– Built-in circuit breaker fault protection

– Two heavy load relays and four signal output relays

– Matrix of output relays for routing the start or trip signals of the protection stage to the desired output relays

– Local display of measured values, set values and data recorded during faults

– Reading and writing of set values via local display and front panel pushbuttons or via the serial interface and fiber optic bus of the higher-level system

– Self-monitoring system for continuous monitoring of electronics and microprocessor operation

Microprocessor operation

– Powerful software support for relay parameterization, reading of measured and logged values, events, etc., and

Powerful software support for relay parameterization, reading of measured and recorded values, events, etc., and storage of readings

– Member of the SPACOM product family and ABB’s distribution automation system

– CE marking according to the EU EMC directive

ABB SPAD346C Integrated Differential Relay

Features

Integrated three-phase differential relay, overcurrent relay and earth fault relay

Stabilized three-phase differential relays provide winding short-circuit and turn-to-turn fault protection for two-winding transformers and generator-transformer units, and winding short-circuit protection for generators.

Earth fault protection for transformer windings on the HV and LV side according to the required principle:

Stabilized differential current principle, high impedance principle, calculated or measured residual current principle or neutral current principle

Three-stage overcurrent protection for transformer and generator as well as two-stage backup protection for earth fault protection.

Differential relays with operating characteristics that can be easily adapted to different applications Short operating times, stable operation even in the event of partial saturation of the current transformer.

Prevents unwanted operation in the event of faults and transformer inrush currents outside the protective field.

Blocking based on the ratio of the second harmonic to the fundamental component of the differential current prevents unwanted operation in the event of transformer inrush currents.

Blocking based on the ratio of the fifth harmonic to the fundamental component of the differential current prevents unwanted operation in the event of transformer overexcitation.

– If the ratio of the fifth harmonic to the fundamental component of the differential current increases at high overvoltages, this blocking condition can be eliminated

Double-winding transformer protection without transformers – digital vector group matching on HV and LV side

Wide range of CT ratio corrections – precise corrections via digital settings Sensitive phase current and phase angle displays for easy checking of measurement circuits

Emerson DeltaV Distributed Control System Power Modules

Introduction

Power – without it, your system would not function. deltaV™ high-capacity power supplies provide you with the most efficient and reliable power solutions available.

DeltaV high-capacity power supply kits power system electronics and ffeld. This is all the power you need for your DeltaV system.

Benefits

Easy to use. DeltaV High Capacity Power Supplies provide reliable 12 V and 24 VDC power for DeltaV system power and bus ffeld power needs.

They mount easily on T-shaped DIN rails!

Increased availability. Redundant modules based on active MOSFET technology offer higher efficiency and lower voltage drop than conventional diode modules, resulting in less heat dissipation and higher system reliability.

Flexible and Cost-Effective DeltaV Bulk power supplies are flexible and cost-effective to use because of the ability to utilize external redundant modules, for example, if load sharing is required.

For example, if load sharing is required.

Models are available with and without conformal coating.

Small footprint DeltaV Bulk Power Supplies have a small, competitive footprint!

Emerson DeltaV Network Smart Switches

Benefits

Plug-and-play installation. Smart Switches feature a DeltaV-compatible setup that installs into the DeltaV network right out of the box.

They require no user configuration to fully support DeltaV network communications. In addition

The default configuration cannot be changed by the user, so you don’t have to worry about installing an incorrectly configured switch.

Automatic lockout prevents unauthorized network connections – Disabling unused network connections is a “best security practice” that helps you comply with plant security policies.

Disabling unused network connections is a “best security practice” that helps you comply with factory security policies.

With the switch’s built-in one-click lockout feature, you can automatically lock out all unused network ports on your system with the click of a button in the DeltaV application.

Full range of switch hardware configurations.

DeltaV network switches are available in a variety of hardware solutions. From 24-port rackmount units to fixed-port and modular field-installable switches.

DeltaV network switches are available to meet a variety of network requirements.

These switches are all you need to implement a DeltaV network.

DeltaV network switches replace currently supported Cisco and Hirschmann switches for implementing DeltaV control networks.

The VE6046. VE6047. and VE6048 DeltaV Smart switches can be used in applications that previously used Cisco switches.

The VE6041. VE6042. and VE6043 Smart Switches can be used in any application where DIN rail field mounting of switches is required.

In most cases, DeltaV network switches are a direct replacement for our existing supported managed switches.

Fully supported by Emerson. As an Emerson product, these DeltaV network switches are fully supported by Emerson.

Fully supported by Emerson. You can get full technical support, warranty support, product support, and education from our global service centers.

All provided by Emerson. In the unlikely event that your switch fails, smart switches are also included in the Rapid Module Replacement Program, so you can get a replacement quickly.

Emerson DeltaV™ Redundant Controller

Benefits

Uninterrupted control operation. By installing redundant M-Series, S-Series, and PK controllers, you create a “safety net” that

protects your process from unexpected controller failures. In the event of a hardware failure, a backup controller is always available to keep your control and process up and running.

Online upgrades. Installing a redundant DeltaV controller allows you to upgrade your DeltaV system online.

New software can be installed into the backup controller online without disrupting operations.

Once the upgrade is complete, the backup controller is automatically configured and available, allowing you to switch to the new ffrmware without interrupting your process.

Once the switchover is complete, the original active controller can be upgraded. In addition, MQ controllers can be upgraded online to MX controllers.

SQ controllers can be upgraded online to SX controllers. This ensures that your system is always ready to expand as your control strategy evolves.

Automatic commissioning. The system automatically detects, commissions, and downloads spare controllers so you can safely replace equipment.

Add redundancy online by simply installing a new 2-wide backplane with system power and MQ, MX, SQ or SX controllers.

The SZ Controller Carrier or Dual Universal Safety Carrier provides 2 slots for SZ controllers, so there is no need to add anything other than additional SZ controllers.

PK controller carriers also provide 2 slots, so simply add a PK controller to an existing carrier.

The engineering database is automatically updated and the spare controller can be activated by simply assigning and downloading a controller redundancy license, all without interrupting the process.

There are no dip switches, jumpers or addresses to assign. The backup controller automatically assigns the proper backup address and starts working, protecting your process.

Bufferless Transitions The DeltaV controller is designed for bufferless control transitions from the active controller to the standby controller.

During this time, the output channels maintain their output state until the switchover is complete and the control module begins execution.

The control module uses signal status to ensure that all I/O channels are normal before taking control action on them.

All output signals are synchronized via the I/O readback function to ensure that control calculations are made based on the current output state.

When using CHARM or DeltaV Classic I/O cards with or without Foundation™ ffeldbus devices.

This ensures an uninterrupted transfer of control during switchover.

Search for products

Back to Top
Product has been added to your cart