Fanuc Field Control Environmental Specifications
Field Control Environmental Specifications
Vibration
Noise
Temperature
Humidity
Modules perform well where vibration is a factor. Modules are installed
on a panel-mounted DIN rail using the clamp supplied, and with the
panel-mounting feet secured. For information about vibration
standards, please see the Conformance to Standards document (GFK-1179).
Modules are resistant to noise levels found in most industrial applications
when installed according to accepted practices, including proper separation
of wiring by voltage and power level. Modules must be installed on a
conductive (unpainted) DIN rail. The DIN rail is an integral part of the
grounding system.
Modules are tested to the specifications listed in the Conformance to
Standards document (GFK-1179).
Modules operate reliably in ambient air temperatures from 0C (32F)
up to 55C (131F).
Storage temperatures are ±40C (±40F) to +85C (185F).
5% to 95%, non-condensing.
For detailed installation information, please see:
Chapter 2 of this manual. It describes installation and wiring for the Bus Interface
Unit module and terminal block.
Chapter 2 of the Field Control I/O Modules User’s Manual. It summarizes installation
instructions for modules and terminal blocks. Detailed installation instructions are
also packed with individual Field Control modules.
The individual module datasheets included in the Field Control I/O Modules User’s
Manual, which provide specific module wiring information.