8205-TI-IS 8-channel Analog Input I/O Modules MODULE SPECIFICATION
Resolution
• 16 bits
Common mode rejection
• >87 dB @ 50/60 Hz
Series mode rejection
• >50 dB @ 50/60 Hz
Common mode voltage between channels
• ± 5 V (max.)
Absolute maximum input voltage
• ± 30 V
Isolation (any channel to Railbus)
• 60 V peak
CONFIGURABLE PARAMETERS
Sensor type
• User selectable
Alarms
• High and low
Input dead zone
• User defined value
Selectable input filtering
• Off / 2 reading avgerage / running avgerage
Drive on open circuit fault
• Disabled / upscale / downscale
Channel status
• Active / Inactive
Cold junction compensation
• Enable / disable / channel number
RESPONSE TIME
Analog signal change to availability on Railbus
• 600 ms (max.)