Welcome to the official website of CNIACS Automation Technology Co., Ltd!

Distribution AF-60 LP™ Micro Drive Derating for Ambient Temperature

Derating for Ambient Temperature

 The ambient temperature measured over 24 hours should be at least 5 °C lower than the max. ambient temperature.

 If the frequency converter is operated at high ambient temperature, the continuous output current should be decreased.

 The frequency converter has been designed for operation at max 50 °C ambient temperature with one motor size smaller than nominal. Continuous operation

 at full load at 50 °C ambient temperature will reduce the lifetime of the frequency converter.

Derating for Low Air Pressure

 The cooling capability of air is decreased at low air pressure.

 For altitudes above 2000 m, please contact GE .

 Below 1000 m altitude no de-rating is necessary but above 1000 m the ambient temperature or the maximum output current should be decreased.

 Decrease the output by 1% per 100 m altitude above 1000 m or reduce the max. ambient temperature by 1 degree per 200 m

Distribution AF-60 LP™ Micro Drive Protection and Features

Protection and Features:

 • Electronic thermal motor protection against overload.

 • Temperature monitoring of the heatsink ensures that the frequency converter trips in case of overtemperature

 • The frequency converter is protected against short-circuits between motor terminals U, V, W.

 • If a motor phase is missing, the frequency trips and issues an alarm.

 • If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).

 • Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit voltage is too low or too high.

 • The frequency converter is protected against earth faults on motor terminals U, V, W

Derating for Ambient Temperature

 The ambient temperature measured over 24 hours should be at least 5 °C lower than the max. ambient temperature.

 If the frequency converter is operated at high ambient temperature, the continuous output current should be decreased.

 The frequency converter has been designed for operation at max 50 °C ambient temperature with one motor size smaller than nominal. Continuous operation

 at full load at 50 °C ambient temperature will reduce the lifetime of the frequency converter.

Electrical Distribution AF-60 LP™ Micro Drive Fuses

Fuses

 Branch circuit protection:

 In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuited and

 overcurrent protected according to national/international regulations.

 Short circuit protection:

 GE Drive is suitable for a circuit capable of supplying a maximum of 100,000 Arms (symmetrical), 480 V maximum.

 Overcurrent protection:

 Provide overload protection to avoid overheating of the cables in the installation. Overcurrent protection must always be carried out according to national

 regulations.

 Non UL compliance:

 If UL/cUL is not to be complied with, GE recommends using the fuses mentioned in the below table, which will ensure compliance with EN50178/IEC61800-5-1:

 In case of malfunction, not following the fuse recommendation may result in damage to the frequency converter

Electrical Distribution AF-60 LP™ Micro Drive Safety Instructions

Safety Instructions

• Make sure the frequency converter is properly connected to earth.

 • Do not remove mains connections, motor connections or other power connections while the frequency converter is connected to power.

 • Protect users against supply voltage.

 • Protect the motor against overloading according to national and local regulations.

 • The earth leakage current exceeds 3.5 mA.

 • The [OFF] key is not a safety switch. It does not disconnect the frequency converter from mains.

Fuses

 Branch circuit protection:

 In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuited and

 overcurrent protected according to national/international regulations.

 Short circuit protection:

 GE Drive is suitable for a circuit capable of supplying a maximum of 100,000 Arms (symmetrical), 480 V maximum.

 Overcurrent protection:

 Provide overload protection to avoid overheating of the cables in the installation. Overcurrent protection

must always be carried out according to national  regulations.

ABB Control Panels CP600 TrueType fonts

TrueType fonts.

Multilanguage applications. Easily create and manage your applications in multiple languages to

meet global requirements. Far East languages are supported. Tools available in PB610 Panel Builder

600 support easy third-party translations and help reducing development and maintenance costs of

the application.

Data display in numerical, text, bargraph, analog gauges and graphic image formats.

Rich set of state-of-the-art HMI features: Data acquisition, alarm handling, scheduler and timed

actions (daily and weekly schedulers, exception dates), recipes, users and passwords, e-mail and

RSS feeds, rotating menus.

Includes support for a set of communication drivers.

Multiple drivers communication capability.

Remote monitoring and control. Client-Server functionality.

Offline and online Simulation with PB610 Panel Builder 600.

Powerful scripting language for automating HMI applications. Script debugging improves efficiency

in application development.

Rich gallery of vector symbols and objects.

Project templates.

ABB Control Panels CP600

The Control Panels combine state-of-the-art features and top performance with an outstanding design.

They are the ideal choice for all demanding HMI applications including factory and building automation.

These Control Panels have been designed to run the PB610 Panel Builder 600 software.

PB610 Panel Builder 600 Runtime included. Full compatibility with PB610 Panel Builder 600.

Full vector graphic support. Native support of SVG graphic objects.

Transparency and alpha blending.

Full object dynamics: Control visibility and transparency, move, resize, rotate any object on screen.

Change properties of basic and complex objects.

TrueType fonts.

Multilanguage applications. Easily create and manage your applications in multiple languages to

meet global requirements. Far East languages are supported. Tools available in PB610 Panel Builder

600 support easy third-party translations and help reducing development and maintenance costs of

the application.

ABB NTDI02 Digital I/O Termination Unit How to Use this Instruction

Installation

Explains the physical installation, wiring and cable

requirements, fuse requirements, dipshunt settings, jumpers

settings and handling of the termination unit.

Maintenance Contains a maintenance schedule.

Repair and Replacement

Explains how to replace the termination unit.

Dipshunt and Jumper Settings

Provides detailed diagrams for dipshunt and jumper settings

for specific modules.

How to Use this Instruction

Read this instruction in sequence. It is important to become

familiar with the entire contents of this instruction before

using the termination unit. Refer to a specific section for infor

mation as needed.

1. Perform the steps in the installation section.

2. Refer to the maintenance section for scheduled mainte

nance requirements.

3. Refer to the repair and replacement procedures to replace

a termination unit.

ABB NTDI02 Digital I/O Termination Unit Installation

Installation

Explains the physical installation, wiring and cable

requirements, fuse requirements, dipshunt settings, jumpers

settings and handling of the termination unit.

Maintenance Contains a maintenance schedule.

Repair and Replacement

Explains how to replace the termination unit.

Dipshunt and Jumper Settings

Provides detailed diagrams for dipshunt and jumper settings

for specific modules.

How to Use this Instruction

Read this instruction in sequence. It is important to become

familiar with the entire contents of this instruction before

using the termination unit. Refer to a specific section for infor

mation as needed.

1. Perform the steps in the installation section.

2. Refer to the maintenance section for scheduled mainte

nance requirements.

3. Refer to the repair and replacement procedures to replace

a termination unit.

ABB NTDI02 Digital I/O Termination Unit Description

Description

The NTDI02 termination unit is a seven-by-seven inch square

printed circuit board. The board contains:

• Two fuses.

• 16 programmable dipshunts.

• 16 user configurable jumpers.

• Four terminal strips.

• One cable socket.

• Two power source Faston connectors.

• One system common Faston connector.

Instruction Content

This instruction contains the following sections:

Introduction

Provides an overview of the NTDI02 termination unit.

Installation

Explains the physical installation, wiring and cable

requirements, fuse requirements, dipshunt settings, jumpers

settings and handling of the termination unit.

Maintenance Contains a maintenance schedule.

Repair and Replacement

Explains how to replace the termination unit.

Dipshunt and Jumper Settings

Provides detailed diagrams for dipshunt and jumper settings

for specific modules.

ABB NTDI02 Digital I/O Termination Unit Overview

Overview

Intended User

Section 1

The NTDI02 Digital I/O Termination Unit is a Harmony rack

I/O device that is part of the Symphony Enterprise Manage

ment and Control System. It provides a signal path for up to

16 input signals to the following I/O modules. The inputs are

used by the controller to monitor and control a process.

• Analog output module (IMASO11).

• Digital input module (IMDSI13. IMDSI14. and IMDSI22).

• Pulse input module (IMDSM04).

• Digital output module (IMDSO14 and IMDSO15).

• Frequency counter module (IMFCS01).

Figure 1-1 shows the Harmony rack I/O architecture. A Har

mony area controller and the Harmony rack controllers can

use the rack I/O module and termination units for I/O interface.

Personnel installing, operating, or maintaining the NTDI02 ter

mination unit should read this instruction before performing

any installation, operation, or maintenance procedures. Instal

lation requires an engineer or technician with experience

handling electronic circuitry. Those working with the NTDI02

termination unit should have experience working with and

know the precautions to take around AC/DC power. A knowl

edge of the Symphony system and electronic principles is also required.