A-B 1746-MPM Mold Pressure Module Wiring Notes
Wiring Notes
• Ground cable shields at one end only.
• Isolate signal wiring from power lines and sources of electrical noise.
• Do not exceed 10V dc on any input terminal.
• Outputs +Exc, +T/R, and -T/R must have a minimum load of 1K ohms.
referenced to analog common.
Module I/O
Inputs
The module has two independent channels that you configure to process
signals from machine sensors (default) or from the SLC output image table
across the backplane.
Outputs (Summary Data)
The module processes a frame of summary data for each molding cycle,
and alternately makes available the previous frame for display. It does this
for channels 1 and 2. Your ladder logic can read summary data from the
module’s M0/M1 files. You can observe summary data displayed on a PC
equipped with DARTWin software. The PC must be linked to the module
with DARTNet network from RJG Technologies, Inc.
Configure the SLC Processor (including I/O, M0/M1, and G file)
This procedure is based on RSLogix500 programming software, version
2.0 or later. For other software, the procedure may vary.
Configure the SLC processor, I/O, size of M0/M1 files, and G file offline
to match your system layout.
1. With the File pull-down window, open the ladder file associated with
this project, or create a project (ladder file) for it.
2. If you have not already done so, select the Controller Properties icon
and launch it. Then select/enter the type of SLC processor.
3. Select the I/O Configuration icon and launch it. Then select/enter:
A. Slot number in the I/O chassis for this module
If using this module in a Pro-Set 200 Injection Control System,
assign this module to slot 7.
B. Module ID (12935), entered under “Other” in the I/O Module window.
Important: When you enter the module ID, the processor automatically
reserves the required number of I/O image table words. The location of
those words in the I/O image table is determined by the module’s slot
location in the I/O chassis. Slot location is a required addressing unit.
For example, I:e.6 locates the 6th word in the block of input image table
words assigned to the module in slot e that you entered in A, above.
C. If you have not already done so, enter the size of I/O chassis and the type of power supply.
4. Select the Adv Configuration icon and launch it.
Then select/enter:
A. Length of M0/M1 files at 106 words, each (listed in section 11).
B. Length of G file at 94 words.