ABB REG216 Processing unit 216VC62a

Processing unit 216VC62a

– 32-bit processor type 80486DX-2

– Application software in Flash EPROM

– Run data stored in RAM

– Settings on non-volatile flash EPROMs

– Potential-free RS-423 interface for PC operation

– Connection to control station via message transmission

– Time clock synchronization for time stamping of events

– Non-volatile event and disturbance memory (gold capacitor buffer)

– Space required: two racks

Analog input unit 216EA62

– 24 inputs sampled simultaneously, 6 per group

– Sampling frequency 600 (720) Hz, power supply frequency 50 (60) Hz

– Space required: two rack partitions.

Digital Output Unit 216AB61

– 32 outputs for controlling relays that output auxiliary relay assemblies

– Short-circuit proof

– Front panel LEDs to indicate activated relays

– Space required: one rack partition.

ABB REG216 Parallel bus and electronics unit

Parallel bus and electronics unit

The electronics units are of plug-in design and are mounted in equipment racks

with a standard size of 19 inches 6U (1U = 44.45 mm).

This rack can be divided into 21 standard partitions.

The data exchange via the parallel bus B448C is controlled and monitored by all available devices.

The protection system is based on a data bus with digital signal processing for most functions;

signal conditioning, analog and digital inputs, A/D conversion, processing and signal output.

The components of the system include

– Static plug-in units, which exchange data via a powerful parallel bus

– Interfaces to the process (main system, station equipment), isolated from the digital processing unit.

Device rack 216MB66/216MB68 and parallel bus B448C

The main features of the parallel bus B448C are

– Specification based on IEEE P 896 (Future Bus)

– Time multiplexing of address and data (16 bits)

– Asynchronous data transfer with handshaking

– Integrity check for each data exchange

– Up to 32 masters with the same status actively access the bus

– Internal 24 V auxiliary power supply common to all electronics units;

redundant 24 V power supplies are available.

ABB Requirements REF610 Feeder Line Protection Relay

Requirements

To ensure correct and safe operation of the relays, it is recommended that preventive

maintenance be carried out every five years on relays operating under specified conditions;

See table 4.1.-1 and section 5.2.4. Technical Data.

When used for real-time clock or logging data functions, the batteries should be replaced every five years.

Configuration

By appropriately configuring the output contact matrix, signals from the protection

level can be used as contact functions. The start signals can be used for

for blocking cooperating relays and for signaling.

The following figure shows the default configuration of the relay:

all trip signals are routed to trip the circuit breaker.

In the first example in Figure 4.2.-1. the residual current is measured by

the iron core balancing current transformer and the output contacts are

connected to enable the automatic reclosing function.

In the second example in Figure 4.2.-2. the residual current is measured through

the trimming connection of the phase current transformer and the output contacts are connected

to enable the trip lockout function with an external reset switch.

ABB REF610 Feeder Line Protection Relay Applications

Applications

The REF610 is a multifunctional relay designed primarily for the protection

of incoming and outgoing lines in medium voltage distribution substations.

In industrial and utility applications, the relay can also be used as backup

protection for motors, transformers and generators.

The relay incorporates a number of protection features including three levels of overcurrent protection,

two levels of non-directional ground fault protection and thermal protection to

provide comprehensive overcurrent and ground fault protection.

An optional arc protection function can be used to detect arcing conditions in air-insulated metal-clad

switchgear,and an automatic reclosing function can be used to automatically clear overhead line faults.

These features further expand the range of applications for the relays.

The large number of digital input and output contacts allows a wide range of applications.

The following figure shows the default configuration of the relay:

all trip signals are routed to trip the circuit breaker.

In the first example in Figure 4.2.-1. the residual current is measured by

the iron core balancing current transformer and the output contacts are

connected to enable the automatic reclosing function.

ABB REF610 Technical Reference Manual

Feeder protection relays

Technical Reference Manual

* Multiple language support

* User-selectable password protection for the HMI

* Display of primary current value

* Demand value

* All settings can be modified via PC

* Optical front communication connection: wireless or cable

* Optional rear communication module with plastic fiber optic, combined fiber optic (plastic and glass) or

RS-4 connection.

(Optional rear communication module with plastic fiber optics, combined fiber optics (plastic and glass)

or RS-485 connection for use with the

SPA bus, IEC 60870-5-103. or Modbus (RTU and ASCII) communication protocols for system

communication.

* Optional DNP 3.0 rear communication module with RS-485 connection for system communication using

DNP 3.0 communication protocols

* Battery backup for real-time clock

* Battery charge monitoring

* Continuous self-monitoring of electronics and software

* Removable plug-in unit

ABB REF610 Feeder protection relays

Feeder protection relays

Technical Reference Manual

REF610 1MRS755310* Two galvanically isolated digital inputs and three additional galvanically isolated

digital inputs on the optional I/O module.

Two galvanically isolated digital inputs and three additional galvanically isolated digital inputs on optional

I/O modules

* Interference logger:

* Recording time up to 80 seconds.

* Triggered by one or more internal or digital input signals

* Records four analog channels and up to eight user-selectable digital channels

* Adjustable sampling rate

* Non-volatile memory for

* Up to 100 time-stamped event codes

* Set values

* Interference logger data

* Time-stamped logging data for the last five events

* Number of AR shots and protection phase starts/trips

* Operating indication messages and LEDs showing status in case of power failure

* HMI with alphanumeric LCD and navigation buttons

* Eight programmable LEDs

ABB REF620 IEC Feeder Protection Key benefits

The REF620 is a member of the 620 Protection, Measurement and

Control product family within the ABB Relion® product family.

Key benefits

Protection, control, monitoring and management integrated in a single relay provides

a compact and versatile solution for public and industrial power distribution systems

Wide range of protection and control functions, either with sensors or conventional CTs and PTs

Functional scalability and wide range of applications allow users to easily

customize configuration applications to meet specific requirements

Pluggable design for quick installation and testing

Large LCD screen with single-line graphic display, accessible locally

or via an easy-to-connect and navigate HMI Thoughtful product lifecycle service

Key Features

Wide range of protection and control functions for incoming or outgoing applications

Multi-frequency conductive earth protection package with high sensitivity and selectivity

State-of-the-art, fast short-circuit and earth fault localization

Several optional function packages – for distributed generation, capacitors, basic motor and arc-light protection

Supports IEC61850 Version 1 and Version 2. including redundant HSR and PRP, GOOSE and IEC61850-9-2

Supports Modbus, DNP3. IEC 60870-5-103 communication protocols and different time

synchronization methods, including IEEE 1588 v2 precision time protocols

ABB ACS800 EconoPACK+ IGBT modules to TIM foil

Overview

TIM foils or otherwise known as graphite sheet have been introduced in use in ACS800 mod

ules using EconoPACK+ IGBT as part of normal continuous improvements in the ACS800

product family. Benefits of using TIM foils in comparison to thermal grease are easier installa

tion and more durable heat transferring properties for longer periods of time. Durability par

ticularly improved in a cyclic application.

Where and how to use

TIM foils are used to transfer the heat generated in the IGBT’s to the heatsink. Full instruc

tions on how to install TIM foils is described in document delivered with TIM IGBT spare part

kits. It’s possible to use a mix of IGBT’s with thermal grease and TIM foils. In parallel con

nected R8i modules it’s also possible to use a mix of modules using TIM foils and thermal grease.

ABB AOI 2.0 Drive Control Emulation

AOI 2.0 Drive Control Emulation

This Add-on Instruction (AOI) is designed to be used in

places where the user doesn’t want to have to modify

the existing control code for Rockwell Drives. The AOIs

and UDTs are already setup to mimic the existing control

and status tags, so just find and replace the existing tags

with the newly created ABB tags and the existing RSLogix

5000 code will control the ABB drive seamlessly. Built in

scaling for customized data is available.

Supported Profile Types

• PF520 series

• PF750 series

More to come in future development

Benefits

• Benefit from pre-defined tag descriptions that mimic

tag descriptions in existing Rockwell drives

• Minimize commissioning cost

• Quickly replace existing drive with ABB without having

to rewrite PLC code

• Leverage modular programming to easily copy and

paste Add-On Instruction for additional drives

• Enjoy the flexibility and versatility of ABB drives

connected to EtherNet/IP and ControlNet network

ABB Let’s connect Drop-in connectivity to Logix5000 controllers Benefits

Benefits

• Reduce development time and simplify diagnostics with

pre-defined tag descriptions and data types

• Minimize commissioning cost

• Create consistent PLC code regardless of programmer

• Easily rename tag description to an installation-specific name

• Leverage modular programming to easily copy and paste

Add-On Instruction for additional drives

• Save time and money by re-using the same User Defined

Data Type for duplicate drives

• Enjoy the flexibility and versatility of ABB drives connected

to EtherNet/IP and ControlNet networks

AOI 2.0 Drive Control Emulation

This Add-on Instruction (AOI) is designed to be used in

places where the user doesn’t want to have to modify

the existing control code for Rockwell Drives. The AOIs

and UDTs are already setup to mimic the existing control

and status tags, so just find and replace the existing tags

with the newly created ABB tags and the existing RSLogix

5000 code will control the ABB drive seamlessly. Built in

scaling for customized data is available.

Search for products

Back to Top
Product has been added to your cart