“Fail-safe” function
If the electrical supply power fails, the positioner output 1 is
depressurized, and the pneumatic actuator’s return spring
moves the valve to the defined safe position. In case of a
double-acting actuator the second output 2 is additionally pressurized.
Change from two to one column
“Fail-freeze” function
If the electrical supply power fails, the positioner output 1 (and
2. if applicable) is closed and the pneumatic actuator stops
(“freezes”) the valve in the current position. If the compressed
air supply power fails, the positioner depressurizes the actuator.
The TZIDC-200 is an electronically configurable positioner with
communication capabilities designed for mounting to
pneumatic linear or part-turn actuators. It features a small and
compact design, a modular construction, and an excellent
cost-performance ratio.
Fully automatic determination of the control parameters and
adaptation to the final control element yield considerable time
savings and an optimal control behavior.