Configuring Your SLC Processor, Off-line

This procedure assumes you are using RSLogix500E Programming Software,

version 2.10 or later. For other software, the procedure may vary.

1. Open your 1746-QV project, VELMOD.

2. Configure the type of SLC processor. To do this:

A. Open the file, Controller Properties.

B. Select the SLC processor type and click OK.

3. Configure the rack size, module slot, and module ID:

A. Open the file, I/O Configuration.

B. Select the rack size.

C. Highlight the slot number for the module.

D. From the list of modules, scroll to 1746-QV and double–click.

If the module is not listed:

– Scroll to Other and double-click.

– Enter the module’s ID (13115) and double-click.

4. Size the “G” file:

A. Highlight 1746-QV (or 13115 if module was not listed).

B. Click [Adv Config].

C. In the dialog box, enter a G-file length of 7.

D. Press [Edit G Data].

We used values from the ladder logic example (appendix B).