The positioner safety function is declared as Type A element
with HFT=0 according to IEC 61508 capable to be used for SIL
Functional Safety Functions up to SIL 2.
According to IEC 61508-2. 7.4.7.4 a useful lifetime, based on
experience should be assumed.
The components of the positioner do not contain any specific
components with a reduced useful lifetime that are contributing
to the dangerous undetected failure rates.
Because the positioner is a moving masses system supplied by
instrumented air the final device usage and environmental
operating conditions (e.g., no/many open-close cycles,
good/bad supply air quality) will have an impact on the usefullifetime.
Therefore, the useful lifetime should be evaluated by the end
user according to the final plant experience data.
The Periodic Proof-Test methods within chapter Periodic Proof
Test and Maintenance on page 9 are suggested to validate the
correct safety function.
When final plant experience, proof testing and related field
monitoring data indicates a limiting useful lifetime by related
operating conditions, then the plant experience-based lifetime
must be used and considered on the failure rates, proof-test
intervals, and replacement intervals.