Mounting

The LSM mounts in two slots of a Bulletin 1771 Series B, I/O chassis. Mounting dimensions will vary with the size of the chassis selected. 

Refer to the appropriate 1771 literature for specific dimensions.

Power Supply

The LSM backplane power requirement is 1.1A at 5V DC. Refer to the appropriate 1771 literature for additional information on available power supply current.

Chassis Grounding

For correct and reliable performance, the grounding recommendations specified for Allen–Bradley PLC systems must be followed.

Swing Arm

The LSM requires the use of a Cat. No. 1771-WC (10 position, gold contacts) Swing Arm.

Wiring

There are two sets of terminals associated with the LSM; a 10 position swingarm and an 8 position fixed terminal block. 

All customer wiring to the LSM is accomplished via these terminals on the front of the module. 

The 10–position swingarm is used to make all of the voltage (PT) connections to the module as well as the Load Share connections. 

These connections are designed to accommodate wire size 0.5 mm2 (22 AWG) through size 2.0 mm2 (14 AWG). 

The 8–position fixed terminal block is used to make all of the current (CT) connections. 

These connections are designed to accommodate gauge wire size 0.5 mm2 (22 AWG) through ring lugs size 3.25 mm2 (12 AWG). 

Phasing and polarity of the AC current and voltage inputs and their relationship are critical for the correct operation of the unit. 

Figure 2.1 through Figure 2.5 shown on Pages 2–7 through 2–11 provide wiring diagrams to help ensure correct installation. 

Two (2) conductor shielded wire (22 gauge or greater) should be used for Load Share wiring.

The shield shall be grounded at the PLC Chassis ground point only.