Welcome to the official website of CNIACS Automation Technology Co., Ltd!

ABB REG216 Digital Generator Protection Module Features

Functional Features

– Modular hardware

– Selectable protection functions

– Multiple applications

– Computerized menu-assisted setup

– All-digital signal processing

– Continuous hardware self-monitoring

– Cyclic test program mainly performed by software

– Parameterization and recording of set values via PC

– Display of measured values

– Event display, acknowledgement and printing

– Interference logging

– Self-logging

– Long-term stability

– Communication and coordination with control stations

– Available in two design versions: REG216 / REG216 Classic

ABB REG216 Digital Generator Protection Module Interfaces to the main system


All hardware can be housed in a single compartment, which provides further shielding against inductive interference and physical protection against dust, etc.

All hardware can be accommodated in a single compartment, which provides further shielding from inductive interference and physical protection from dust.

The REG216 is available in 17 predefined rack configurations with a limited number of I/Os, but is equipped with the same SW library as the classic system.

Protective relays for other functions are not part of the EG216 and can be installed in compartments and interconnected with the REG216 accordingly.

Interfaces to the main system

The following modular components provide the interface between the REG216 and the power system.

Input transformer assembly

216GW62 This assembly is used to adjust the signal level and to isolate the primary system CT and PT circuits from the electronic circuits of the protective devices.

One PT and two CTs are available to meet different accuracy and dynamic performance requirements.

Up to 12 transformers can be accommodated, selected according to application requirements. Up to four components, i.e. 48 inputs, can be used.

Auxiliary relay and optocoupler assembly 216GD61a

This assembly is for use with the REG216 version. It provides eight trip relays,

Each relay has powerful potential-free trip contacts (with surge circuit), 16 auxiliary relays and 16 optocouplers.

relays and 16 optocoupler input circuits. Up to four assemblies are available.

Input Auxiliary Relay Assembly 216GE61

Up to 16 auxiliary relays to provide full potential isolation for digital input signals.

ABB REG216 Digital Generator Protection Module Building Engineering

Construction

Hardware

The REG216 device consists of two main components, which are physically separated from each other and connected by standard prefabricated shielded cables

Connected by standard prefabricated shielded cables:

– The main system interface (CT, PT and auxiliary relays), which provides DC isolation and EMI barriers.

Isolation and EMI barrier

– Parallel bus and associated electronic units (e.g. analog inputs and data processors / for signal conditioning and processing).

The complete protection scheme consists of a relatively small number of hardware modules, allowing subsequent expansion of the electronic units and interfaces. Each device frame provides 21 rack spaces.

All hardware can be housed in a single compartment, which provides further shielding against inductive interference and physical protection against dust, etc.

All hardware can be accommodated in a single compartment, which provides further shielding from inductive interference and physical protection from dust.

The REG216 is available in 17 predefined rack configurations with a limited number of I/Os, but is equipped with the same SW library as the classic system.

Protective relays for other functions are not part of the EG216 and can be installed in compartments and interconnected with the REG216 accordingly.

ABB REF610 Feeder Line Protection Relay Product  Features

* Arc protection

* Two lens sensors for arc detection (optional)

* Automatic adjustment of reference level according to backlight intensity

* Arc detection by remote light signal

* Automatic reclosing 1…. .3 times

* Circuit breaker fault protection

* Trip counter for circuit breaker status monitoring

* Trip circuit monitoring with routing of warning signals to signal outputs

* Trip lockout function

* Four accurate current inputs

* User selectable rated frequency 50/60 Hz

* Three normally open power output contacts

* Two change-over signaling output contacts and three additional change-over signaling output contacts on optional I/O module

* Output contact functions can be freely configured according to requirements.

ABB REF610 Feeder Line Protection Relay Product Overview

Product overview

3.1 Purpose of the relay

The feeder protection relay REF610 is a multifunctional protection relay primarily used to protect incoming and outgoing lines in various feeder applications.

The relay is based on a microprocessor environment. A self-monitoring system continuously monitors the operation of the relay.

The human-machine interface includes a liquid crystal display (LCD) that makes local use of the relay safe and easy.

The relays can be controlled locally via serial communications from a computer connected to the front communication port.

Remote control is available through a serial communications bus connected to the rear connector of the control and monitoring system.

3.2. Features

* Three-phase non-directional overcurrent protection with timing or IDMT characteristics and low rectification phase.

* Three-phase non-directional overcurrent protection, high rectification phase

* Three-phase non-directional overcurrent protection, instantaneous stage

* Non-directional ground fault protection with timing or IDMT characteristics, low setting stage

* Non-directional ground-fault protection, high-calibration phase.

* Phase discontinuity protection

* Three-phase cable thermal overload protection

ABB REF610 Feeder Line Protection Relay Technical Description

Outputs

The relay is equipped with

* three power output contacts PO1. PO2 and PO3

* two signal output contacts SO1 and SO2

* three optional signal output contacts SO3. SO4 and SO5

Switch group SGR1…. .8 is used to route internal signals from the protection stage, external trip signals and signals from the automatic reclosing function to the required signal or power output contacts.

The minimum pulse length can be configured as 40 or 80 ms and the power output contacts can be configured as latching.

Trouble Logger

The relay has a built-in disturbance logger that records the instantaneous measured value or the RMS curve of the measured signal.

and up to eight user-selectable digital signals: digital input signals and internal signals from the protection stage.

Any digital signal can be set to trigger the recorder on the falling or rising edge.

Fanuc IC694MDL940 PAC System RX3i Discrete Output Module

The module has sixteen (16) normally open (N.O.) contacts divided into four (4) banks of four (4) outputs each.

Each contact output can operate at 5-30 VDC with a nominal voltage of 24 VDC; 5 – 250VAC at 47 to 63 Hz with a nominal input voltage of 120/240VAC.

Each channel is designed for a 2 Amp lead load, a maximum load per output and a maximum load of 4 Amps per common.

The module has a current draw of 7 mA with all outputs turned on by the 5 V bus on the backplane and 24 mA with all outputs turned on by the relay 135V bus on the backplane.

The IC694MDL940 is a sixteen (3) point relay output module for the Emerson Automation PACSystem RX16i series, formerly manufactured by GE Intelligent Platforms (GE IP).

The module has a single slot width, occupies a single slot on the backplane, and comes with four (4) output groups of four (4) relay outputs each.

The IC694MDL940 relay contacts are normally open (N.O.) contacts or type A contacts. Each output contact is rated for a maximum load of 2 amps pilot load.

Fanuc IC694MDL930 Relay Output Module

About the IC694MDL930

This IC694MDL930 is part of the PACSystem RX3i midrange programmable automation controller (PAC) platform.

It is designed for use as a relay output module with eight (8) independently isolated normally open (N.O.) or A-type contact outputs.

Each output contact essentially has a separate common and dry contact, allowing different voltage types and levels to be connected exclusively to the module.

i.e. 5-30 VDC (nominal 24 VDC) and 5-250VAC (nominal 120/240VAC).

The current capacity of each output channel is 4 amps per output when used with resistive loads and 2 amps per output when used with pilot load devices.

Current capacity is 2 amps per output channel. For UL installations, the maximum load current that the module can withstand is 30 amps and varies according to ambient temperature.

Conversely, the minimum load that the module can withstand is 10 mA, and the module’s output channels have a typical response time of 15 ms between on and off switching, while the module’s maximum backplane current is 2 amps.

The module’s maximum backplane current draw is 6 mA, and all outputs are energized by a 5 VDC bus on the backplane.

All outputs are energized by a relay 70VDC bus on the backplane and the maximum backplane current consumption is 24mA.

The module also supports mounting to 90-30 series backplanes. It can be used as a local output module, mounted on a central processing unit (CPU) chassis, or with an appropriate communications adapter.

Fanuc IC200ALG262 8-Point Analog Current Input Module for VersaMax I/O Series

About the IC200ALG262

The IC200ALG262 is a component module of the VersaMax I/O platform. It is an analog input module designed to support differential current wiring.

It has eight (8) analog input channels designed to receive standard current input signals such as 0-20 mA and 4-20 mA input signals.

This IC200ALG262 is currently manufactured by Emerson Automation. It is ideally suited for connection to analog signal generating instruments such as field transmitters.

for measuring pressure, level, flow, temperature, turbidity, viscosity, speed, and other types of transmitters; for integrating locally mounted panel meters to

remote display; for monitoring the speed output of variable frequency drives (VFDs); for monitoring the position of rotary and linear devices; and other applications.

The IC200ALG262 has a built-in analog-to-digital converter (ADC) circuit with 15-bit conversion resolution. The input channels are arranged in groups.

When configured to receive 4-20 mA, they are capable of detecting power loss and open circuit detection within the module. Each channel has an uplink rate of 7.5 ms.

IC695RMX128 PACSystems RX3i Redundant Memory Switch Module

This IC695RMX128 is a PACSystems RX3i redundant memory switching module manufactured by Emerson Automation (formerly GE Intelligent Platforms (GE IP)).

The module has 128MB of SDRAM user memory and supports operation as a reflective memory network or dedicated link between RX3i CPUs in a redundant configuration.

The module comes with single-mode fiber that supports 2.12 Gbaud fiber networks.

About the IC695RMX128

The IC695RMX128 is the PACSystems RX3i Redundant Memory Exchange Module.

The primary function of the module is to act as a single node on a reflective memory topology or as a dedicated memory module for redundant RX3i CPU pairs.

When used in a redundant CPU configuration, the IC695RMX128 reflects the contents of the IC695CMX128.

With a reflected memory link, any updates on one node are reflected and updated to all other nodes connected to the same network.

Connections are established over a fiber optic network supporting up to 256 nodes.

The module is equipped with 128 MB of reflective memory, and the fiber optic power supply requires an LC-type connector for transmission speeds up to 2.12 Gbaud.

The module operates on supplies of 580 mA @ 3.3 VDC and 220 MA @ 5 VDC.